Outback-power-systems VFX Series International Programming Manual Manuel d'utilisateur Page 24

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 56
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 23
23
STACKING OPTIONS
OutBack International Series FXs can be stacked in one of two con gurations:
1. OutBack Parallel
2. 3-Phase
NOTE: Although stacking 10 FXs is possible, OutBack’s AC hardware only accommodates con gura-
tions of two, four, or eight FXs. A system with eight FXs would require two AC Input/Output Bypass
(IOB) Breaker Kits or installing an external manual bypass; ten FXs would require three IOB kits or an
external manual bypass.
1. Outback Parallel
2-10 FXs are wired to the same 230 VAC output leg or phase.
The Slave FXs can be programmed to remain at di erent power levels (Silent or On depending on
the need) to save energy; the Slaves will come on when the power demand requires them.
This power-saving system is fully automatic and works with or without a MATE connected to the
system, although a MATE is required to program the components. Without a MATE, the user cannot
reprogram.
The AC input (generator or grid) must be 230VAC.
3 kW 230 VAC 3 kW 230 VAC 3 kW 230 VAC
9 kW
230 VAC
LOAD
Vue de la page 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 55 56

Commentaires sur ces manuels

Pas de commentaire